PMU+ is a licenced firmware module that enables synchrophasor streaming using IEEE C37.118.2 protocol.
Stable under highly distorted waveforms
When studying the performance of inverter-basedpower plants, it’s common to encounter voltage and current waveforms that are either chopped or heavily distorted. The PMU+ algorithm used can accurately determine the fundamental frequency phasor set despite all these distortions.
Very high time resolution
The absolute GPS based time synchronisation on the VECTO 3 devices is <100ns. This translates to 4-digit frequency measurement resolution (±0.000250Hz for 50Hz) and an industry-leading ±0.0018-degree phasor angle resolution.
Simultaneous Class-M & Class-P compliance
Most PMU devices need to be configured in either Class-P or Class-M mode. The PMU+ algorithm simultaneously meets both Class-P and Class-M requirements, eliminating the need to configure for Class-M’s accuracy and Class-P’s speed. This is particularly useful when analysing grid stability events that contain very small amplitude information at higher frequencies (~20Hz), where both speed and accuracy are required.
Offline synchrophasor recording
Synchrophasor data is recorded offline and is available for download as part of the existing data streams – without the use of the C37.118.2 streaming protocol. This means that synchrophasor data can be collected throughout the network – without having to rely on expensive broadband communication infrastructure required by the C37.118.2 protocol.
Adds PMU data to current set of
diagnostic information
The PMU+ module allows synchrophasor data to be combined with Power Quality event data, providing an additional data stream with powerful diagnostic capabilities.
The suite of diagnostic data now contains the following:
The PMU+ module retains a long pre-event buffer, which enables detailed analysis of the build-up to & the impact of complex Power Quality (PQ) events. Users can specify the duration of long pre- and post-event synchrophasor data recording, spanning tens of minutes, as part of the PMU+ module set-up process.
Available on Modbus Protocol
Synchrophasor data is accessible via the Modbus protocol interface. This simplifies the integration of the devices as part of plant control strategies.
20ms Modbus Update Rate
The update rate of synchrophasor data via Modbus is once per cycle. This high update rate is required by most plant controllers.