10MHz Sampling Multifunction Power Quality Based Transient Recorder
The 10MHz sampling VECTO TRANSIENT is a multifunction, waveform synchronised, Ed4.0 Class-A power quality based transient recording device, with the ability to store full resolution raw waveforms. A number of triggering conditions can be used to capture events with full 10 MHz diagnostic waveforms, including absolute value exceedance and rate of change exceedances.
The device is permanently GPS or PTP time synchronised to within < 100 ns from absolute time, and offers high accuracy and high-bandwidth analog inputs with selectable input range.
It offers secure Gigabit bandwidth IP integration via Ethernet, Fiber, WiFi and 4G Cellular interfaces. The devices are powered from either AC, DC or POE-Plus sources and offers built-in battery support.
VECTO devices can operate stand-alone or as part of a fleet of permanently connected devices managed by VECTO Grid OS, the big data hosting, visualisation, analysis & reporting software platform. Various add-on software modules are available.
| AC & DC Voltage Inputs | |
|---|---|
| Number of Channels | 4 x screened voltage inputs |
| Measurement Range | 400 VLN, 700 VLL, ±565 VDC |
| Voltage measurement | DC, Single Phase, 3-Phase (Star, Delta) |
| Input impedance/channel | > 1 MΩ |
| AC & DC Current Sensor Inputs | |
|---|---|
| Number of Channels | 4 x screened low voltage broadband inputs |
| Measurement Input Range | ±2.5 VRMS, ±3.6 VDC |
| Impedence/channel | > 1 MΩ |
| Accuracy & Bandwidth | |
|---|---|
| Sampling rate | 10 MHz (±100 ns time synchronised) |
| Analogue bandwidth | >2 MHz |
| Waveform storage rate | 10 MHz |
| ADC resolution | > 18-bit |
| Overall accuracy | < 0.1% |
| Fast transient capturing | ≥ 500 ns |
| Power frequency range | DC, 40-70 Hz |
| Harmonic spectrum | 1-64th (harmonic and inter-harmonic) |
| Higher harmonic bands | DC – 25 kHz (200 Hz bands) |
| Clocks | |
|---|---|
| Onboard precision time source | Battery-backed industrial GPS (3.3 V powered active external antenna) |
| Onboard fall-back time source | Battery-backed real time clock |
| Onboard RTC drift | 10 ppm (320 seconds per annum) |
| External sources | NTP, PTP (IEEE1588-V2) |
| Overall time accuracy | < 100 ns from absolute time (when locked to GPS or PTP) |
| Analogue/Logic Inputs | |
|---|---|
| Number of channels | 4 x voltage inputs |
| Input Voltage Rating | ± 300 VDC |
| Input impedance/channel | > 1 MΩ |
| Relay Outputs | |
|---|---|
| Number of Channels | 4 x galvanically isolated solid-state relays |
| Switch Rating | 1ARMS, 300VRMS (max) |
| Galvanic isolation | 1,000 V |
| Physical | |
|---|---|
| Dimensions | 250 x 135 x 65 (L x W x H) |
| Material | Aluminium plates, plastic collar |
| Weight | 1.9 kg |
| Mounting Options | Portable, DIN Rail, 19” Rack (3U) |
| Electrical connections | Pluggable screw type (screw lock-down) |
| Rated range of operation and storage | -20ºC to 60ºC |
| Operating humidity | 0-95% (non-condensing) |
| Communication | |
|---|---|
| Ethernet | 2 x gigabit ethernet |
| Fibre | 1 x 1000BASE-X SFP cage |
| Cellular modem | 1 x Battery backed industrial 4G module |
| Cellular antennae | 1 x MIMO antenna port |
| Wifi | 1 x industrial WiFi module |
| Wifi antennae | 1 x MIMO antenna port |
| Operating modes | Access Point or Infrastructure Mode |
| USB expansion port | 1 x USB-C (USB2.0–480 Mbit) (powered) |
| Power | |
|---|---|
| Power consumption | < 25 W |
| AC supply voltage range | 90-280 VAC (40-70 Hz) |
| DC supply voltage range | 90-300 VDC |
| Power over Ethernet | IEEE 802.3at compliant |
| Onboard battery | Li‑ION (Replaceable) |
Download the VECTO TRANSIENT Specification Sheet
VECTO devices can operate stand-alone or as part of a fleet of permanently connected devices managed by VECTO Grid OS, the big data hosting, visualisation, analysis & reporting software platform.